Skip to main content

Water Control Solutions

FP 400Y-7BM

The BERMAD Model FP 400Y 7BM is an elastomeric deluge valve, designed for advanced fire protection systems and the latest industry standards. The Double Interlock Pre-Action is suitable for use in systems requiring that water be kept out of the sprinkler piping until an electric detecting device and a sprinkler have both been activated. Electric-Electric double interlock systems include automatic sprinklers attached to a dry sprinkler piping system with a low air pressure switch, along with a supplementary electric detection system which are both wired to a Cross-Zone releasing control panel. Model FP 400Y-7BM Pre-Action System admits water into the sprinkler piping only when both the detection device and the supervised systems simultaneously signal the control panel to trigger the solenoid valve. An anti-flooding feature is provided by using an in-line check valve, which creates an intermediate vented chamber using a Normally Open drip-check. As an option the 400Y 7BM features a visual quarter turn valve position indicator, available with limit switches for remote valve position monitoring.

 
Eigenschappen en voordelen
  • Safety and reliability
    • Time proven, Simple, fail-safe actuation
    • Single piece, rugged elastomeric diaphragm seal – VRSD technology
    • Intermediate anti-flooding chamber
    • Obstacle-free, uninterrupted flow path
    • No mechanical moving parts
  • High performance
    • Very high flow efficiency
    • Straight through flow Y- type body
    • Approved for PN20 / 300 psi
  • Quick and easy maintenance
    • In-line serviceable
    • Quick cover removal without detaching control trim*
    • Swivel mounted drain valves*

* not including 1½” & 2” valves

Toepassingsvoorbeelden

Typical Applications

  • Water sensitive material storage
  • Freezing conditions
  • Computer and electronics rooms
  • Libraries / museums & archives

 

System Installation

A typical installation of the BERMAD model 400Y-7BM features automatic actuation via a solenoid valve and crosszone releasing control panel.

Actuation occurs only when the control panel receives simultaneous electric signals from an electric fire-detection system and a low pressure sensing switch/relay valve.

When fitted with a limit switch, the valve can send a feedback signal to the remote valve position monitoring system.

An inline check valve and drip-check valve create an intermediate vented chamber to ensure against flooding when the valve is closed.

 

Downloads

FP 400Y 7BM Product Page English

FP 400Y TORRENT DELUGE VALVES

FP 400Y Torrent Engineering