Model 43T-PS
- Safety and reliability
-Obstacle-free, uninterrupted flow path
-Time-proven, simple, fail-safe actuation
-Single piece, rugged, elastomeric diaphragm seal – VRSD technology
-No mechanical moving parts
- High performance
-Very low head loss – allows maximum pump capacity
-High flow capacity
-Rated for PN 25bar/365 psi
-Straight-through-flow Y-type body
-Accurate pressure control within 5% of setting
- Specifically-designed for fire protection
-Face-to-face length standardized to ISO 5752, EN 558-1
-Meets the requirements of the industry standards
- Quick and easy maintenance
-In-line serviceable
-Fast and easy cover removal
Typical Applications
- Maintaining minimum suction head to a booster pump
- Over draw prevention in shared supply lines
- Prevention of pump cavitation damage
System Installation
A typical installation of the BERMAD model 43T-PS is where the valve is installed downstream of the pump with a pressure sensing line leading from the valve to the pump intake or suction pipe.
The 43T-PS is especially suited for this function, as it has an exceptionally high flow capacity.
Therefore when pump suction pressure is available and above the pre-set minimum the 43T-PS will be fully open, presenting minimal
pressure loss for delivering the maximum possible volume of water to the fire event.